Loading...
Check NEC conduit fill compliance instantly. Select conduit type and size, wire type and gauge, enter the count, and see if your installation passes code. EMT, IMC, RMC, PVC Schedule 40 and 80 supported.
7.5% fill (40% max)
NEC Reference
Based on NEC Chapter 9, Tables 1, 4, and 5. Fill percentages: 53% for 1 wire, 31% for 2 wires, 40% for 3+ wires. Wire areas include insulation.
Choose from EMT, IMC, RMC, PVC Schedule 40, or PVC Schedule 80. Then pick the trade size from 1/2 inch to 4 inches. The calculator uses NEC Chapter 9 Table 4 internal areas for each combination.
Select THHN/THWN-2 or XHHW-2 insulation type, then pick the wire gauge from 14 AWG to 500 kcmil. Enter how many conductors of that size you plan to install. Wire areas come from NEC Chapter 9 Table 5.
The results panel shows pass or fail status, actual fill percentage versus the NEC maximum, the minimum conduit size that would pass, and the maximum number of wires of that size allowed in the selected conduit.
EMT, IMC, RMC, PVC Schedule 40, and PVC Schedule 80 with all standard trade sizes from 1/2 to 4 inches.
Wire and conduit areas from NEC Chapter 9 Tables 4 and 5. Fill percentages from Table 1. No guesswork.
Green pass or red fail badge with percentage bar. Know immediately if your conduit run is code-compliant.
Shows the smallest conduit that passes NEC fill limits for your wire configuration. Saves material costs.
See exactly how many wires of the selected size fit in the chosen conduit. Plan your runs efficiently.
Built-in reference for the 53/31/40 percent fill rules so you always know which limit applies.
Every wire carrying current generates heat. When you pack too many wires into a conduit, that heat has nowhere to go. The insulation temperature rating is based on adequate ventilation around each conductor. Exceed the fill limit and you create conditions where insulation degrades faster, ampacity must be derated, and in the worst case, the heat can cause insulation failure and arcing. The NEC fill percentages are engineered to prevent these problems while still allowing a reasonable number of conductors per run.
There is also a practical concern: pulling wires through conduit. Even at 40% fill, the friction between conductors and conduit walls during a long pull can be significant. Overfilled conduit makes installation physically difficult and risks damaging the insulation as wires scrape against each other and against the conduit walls during pulling. Most electricians will tell you that just because a wire physically fits does not mean it should go in there.
EMT is the default choice for most indoor commercial and residential applications. It is lightweight, easy to bend, and relatively inexpensive. You connect it with compression or set-screw fittings rather than threading. For exposed outdoor locations, underground runs, or anywhere conduit might take physical abuse, RMC provides the most protection. It is threaded at every joint for a watertight seal.
PVC conduit is the go-to for underground direct-burial applications and in corrosive environments where metal conduit would rust. Schedule 40 is standard for most underground runs; Schedule 80 has thicker walls and is used where the conduit is exposed above ground or subject to physical damage. Note that PVC has slightly smaller internal areas than similarly sized metallic conduit, which can affect your fill calculations.
A typical 20-amp branch circuit uses three 12 AWG THHN conductors (hot, neutral, ground). In 1/2-inch EMT, three number 12 THHN wires occupy about 13% of the conduit area, well under the 40% limit. You could fit up to nine number 12 THHN wires in a half-inch EMT before hitting the 40% fill. But remember that ampacity derating kicks in when you have more than three current-carrying conductors, which is a separate NEC requirement from conduit fill.
For larger feeders, say four 3/0 THHN conductors for a 200-amp service, you need at least 1-1/4 inch EMT. The total wire area is 4 times 0.2679 equals 1.0716 square inches. A 1-1/4 inch EMT has 1.496 square inches of area, and 40% of that is 0.5984 square inches, so 1-1/4 inch actually fails. You would need 1-1/2 inch EMT (2.036 square inches, 40% = 0.8144 square inches), which still fails. Move up to 2-inch EMT (3.356 square inches, 40% = 1.3424 square inches) and the four 3/0 wires fit comfortably.
Common questions about NEC conduit fill rules, conduit types, and wire sizing.
Disclaimer: This Conduit Fill Calculator uses data from the National Electrical Code (NEC). Always verify calculations against the current edition of the NEC and consult a licensed electrician for actual installations. Local codes may have additional requirements.